Multi-Bus Gateway

Technical reference

Device compatibility and protocol roles.

Find your device, see how the gateway connects to it and check the limits of the integration. Each bundled map links to its register definitions and source notes.

documented templates
31
Gateway reference
3.98.2
Source checked

One gateway, explicit protocol roles.

Roles below describe the current release. OPC UA is a server interface. CAN currently receives frames; active CAN communication and transmission are planned.

On narrow screens, scroll the table sideways to see all columns.

Protocol roles and integration boundaries in Community
InterfaceCurrent gateway roleData pathIntegration boundary
Modbus TCP / RTU / ASCII / UDPClient / master Poll devices and execute allowed writes.Writes require explicit permission and template support.
HTTP / JSON inputHTTP client Acquire values from JSON endpoints.Payload fields are mapped through json_path.
HTTP / JSON outputHTTP server / read-only feed Expose live values through a read-only JSON feed, including /api/meters/<id>.Enable the output for the device; this feed does not accept commands.
REST push / webhooksHTTP telemetry publisher Periodically POST JSON telemetry to a configured endpoint or webhook.Configure destination, native/flat format and authentication. Redirects are refused.
MQTTSubscriber + publisher Acquire values, publish telemetry and receive allowed commands.A broker and topic configuration are required.
CAN / SocketCANListener Decode incoming frames using the template.Today: host hardware listen-only mode. Active CAN transmission is planned.
Seplos V2Reader or passive tap Read Seplos V2 BMS values over its ASCII protocol.Read-only; direct polling and inter-pack listening use different maps.
OPC UAOPC UA server Serve values, quality, read timestamps and allowed commands to SCADA/HMI.An OPC UA client for reading PLCs is on the roadmap.
Virtual Modbus metersModbus TCP server Serve existing data as EM24, Fronius Smart Meter or SunSpec maps.Select a freshness policy and bounds for each instance.
InfluxDBTime-series publisher Write history with a disk-backed replay buffer.The buffer is bounded by configured age and point count.

Find the map for your device.

These are bundled maps, not blanket support for every model or firmware from a manufacturer. Match the exact model, transport, register meanings and write permissions before use.

On narrow screens, scroll the table sideways to see all columns.

Bundled device templates and register-map sources
Device / templateInput / mapMapped valuesRegister map & sources
Janitza UMG 512-PROjanitza_umg512_pro FC03 / big4,126
Register map & sources

Modbus Address List

Open register map →
ABB B21 (single-phase)abb_b21 FC03 / big10
Register map & sources

ABB B-series Modbus (2CDC512084D0101); cross-checked vs steefan85/ABB_B23_Energy_Meter and roastedelectrons/ABBEnergyMeter

Open register map →
ABB B23 (3-phase)abb_b23 FC03 / big32
Register map & sources

ABB B23/B24 User Manual 2CMC485003M0201 ch.9 (docs/vendor/meters/abb-b23-b24-user-manual.pdf) — register-for-register confirmed; also cross-checked vs steefan85/ABB_B23_Energy_Meter and roastedelectrons/ABBEnergyMeter

Open register map →
BLE sensor (Theengs / BTHome → MQTT)ble_theengs_sensor MQTT5
Register map & sources

https://decoder.theengs.io/devices/devices_by_brand.html

Open register map →
Carlo Gavazzi EM24 (AV5/AV53, 3-phase)carlo_gavazzi_em24 FC03 / little17
Register map & sources

Victron dbus-modbus-client carlo_gavazzi.py (EM24_Meter) + Carlo Gavazzi EM24-DIN communication protocol

Open register map →
Delta VFD-EL frequency drivedelta_vfd_el FC03 / big16
Register map & sources

Delta VFD-EL User Manual, revision 2016/03 (6ELE, V1.14): Group 9 communication parameters p. 102, function codes p. 105 (03H read n≤20 words, 06H write, 08H loop detection), address list p. 108-110 (2000H-2002H, 2100H-210AH, parameter address GGnnH), Pr 02.00 p. 36. Not yet field-checked: the 0.01 Hz scaling of 2001H, 2101H bit 10, block reads of 2100H-210AH and the Pr 02.01 values are to be confirmed on a VFD022EL43A.

Open register map →
Deye single-phase hybrid inverter (read-only)deye_hybrid_1p FC03 / little64
Register map & sources

Deye single-phase hybrid Modbus map as published by the ha-solarman project (deye_hybrid.yaml, SUN-xK-SG01LP1/SG03LP1/SG05LP1) and cross-read against kellerza/sunsynk (src/sunsynk/definitions/single_phase.py: the same Deye/Sunsynk single-phase firmware; there a negative factor marks a signed register, not an inversion) and Deye's 'Modbus RTU protocol' for single-phase energy storage inverters. Reference only, no code copied. Checked on a SUN-8K-SG05LP1 (protocol 0x0201) on 2026-10-27; each row says whether it was. The GEN port, BMS block and battery settings (0.3.0) come from the same maps; the BMS temperature (319) from the Deye document only.

Open register map →
Eastron SDM120 (single-phase)eastron_sdm120 FC04 / big10
Register map & sources

Eastron SDM120/SDM220 Modbus Protocol (input registers, FC04, float32)

Open register map →
Eastron SDM630 (3-phase)eastron_sdm630 FC04 / big29
Register map & sources

Eastron SDM630 Modbus Protocol V2 (input registers, FC04, float32)

Open register map →
Fronius Smart Meter 65A-3 (RTU)fronius_smart_meter_65a FC03 / little30
Register map & sources

Field-verified against a physical Fronius Smart Meter 65A-3 over Modbus RTU (2026-08-11): |P|<=S per phase, S^2~=P^2+Q^2, PF=P/S, Freq=50Hz.

Open register map →
Fronius inverter (Solar API / HTTP-JSON)fronius_solar_api_inverter HTTP/JSON7
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Fronius inverter, per-phase AC (Solar API / HTTP-JSON)fronius_solar_api_inverter_3p HTTP/JSON6
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Fronius Smart Meter (Solar API / HTTP-JSON)fronius_solar_api_meter HTTP/JSON31
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Fronius installation (Solar API site totals)fronius_solar_api_site HTTP/JSON9
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Fronius SunSpec inverter (int+SF, via datalogger)fronius_sunspec_inverter FC03 / big69
Register map & sources

SunSpec Information Models (int+SF); register map verified live against a production Fronius fleet (raw-frame decode parity, 2026-09-11)

Open register map →
Fronius SunSpec meter (int+SF, via datalogger)fronius_sunspec_meter FC03 / big48
Register map & sources

SunSpec Information Models (int+SF); register map verified live against a production Fronius fleet (raw-frame decode parity, 2026-09-11)

Open register map →
Huawei DTSU666-H meter (via SUN2000)huawei_dtsu666_via_sun2000 FC03 / big21
Register map & sources

Huawei 'Solar Inverter Modbus Interface Definitions', power meter registers 37100-37137; cross-read against wlcrs/huawei-solar-lib (grid_exported_energy 37119, grid_accumulated_energy 37121, power_meter_active_power 37113). Not yet checked on hardware.

Open register map →
Huawei LUNA2000 battery (via SUN2000)huawei_luna2000 FC03 / big23
Register map & sources

Huawei 'Solar Inverter Modbus Interface Definitions', energy storage registers 37000-37048 and 37758-37787; cross-read against wlcrs/huawei-solar-lib (storage_* and storage_unit_1_* definitions). Not yet checked on hardware.

Open register map →
Huawei SUN2000 inverterhuawei_sun2000 FC03 / big56
Register map & sources

Huawei 'Solar Inverter Modbus Interface Definitions' (Huawei SUN2000 Modbus interface, register 30000-32114 tables, device status codes, State/Alarm bit fields); cross-read against wlcrs/huawei-solar-lib register definitions. Not yet checked on hardware.

Open register map →
Generic MQTT (JSON)mqtt_json_generic MQTT3
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Pylontech CAN (BMS → inverter link, listen-only)pylontech_can_inverter CAN (listen-only)30
Register map & sources

Pylontech 'PYLON CANBUS Protocol' V1.2 (2018-04-08); Seplos 'CANBUS Protocol V1.0' (2020, akkudoktor.net mirror); LuxPower 'Battery communication CAN Protocol' V04 (2024-03-13); cross-checked (no code taken) against esphome-yambms packages/yambms/yambms_canbus.yaml (Sleeper85, GPLv3); verified on a 2-minute candump of a Deye SG05LP1 ↔ Seplos V2 bank (tests/fixtures/can/deye_seplos_v2_20261026.candump, listen-only, 2026-10-26).

Open register map →
Samsung MIM-B19N Modbus interface (DVM / EHS)samsung_mim_b19n FC03 / big60
Register map & sources

Samsung DB68-07538A-03 Installation manual, Modbus Interface Module MIM-B19N/MIM-B19NT, Table 2 (Modbus register table), p. 13-16; the addresses match a Node-RED flow that read the same unit (FC3, address 50 x28). Field-checked 2026-10-08 on a DVM-S with an HE hydro kit at IU 0: 0x7FFF on the hot water temperature = no tank sensor. Extra registers: Table 3 of DB68-07538A-03 (2022) for the official IDs; community IDs from ZimKev's MIM-B19N notes (EHS) and the 'More Hidden Registers' list.

Open register map →
Schneider iEM3000 (3-phase)schneider_iem3000 FC03 / big22
Register map & sources

volkszaehler/mbmd meters/rs485/iem3000.go (field-tested; cites Schneider DOCA0005). Official register list saved at docs/vendor/meters/schneider-iem3000-modbus-register-list.pdf (image-only PDF, not machine-parsed).

Open register map →
Seplos BMS V3 bank (via seplos-bms-mqtt)seplos_bms_bank_mqtt MQTT28
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Seplos BMS V3 (via seplos-bms-mqtt)seplos_bms_mqtt MQTT58
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Seplos BMS V2 pack (ASCII protocol, read-only)seplos_bms_v2 Seplos V2 ASCII (virtual map)107
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Seplos BMS V2 pack (inter-pack tap, listen-only)seplos_bms_v2_tap Seplos V2 ASCII (virtual map)22
Register map & sources

No published layout for CID2 0x5A: the Seplos 'BMS communication protocol V2.0' covers 0x42/0x44/0x47/0x51, and no community decoder handled 0x5A (searched 2026-10-26). Layout from the passive capture tests/fixtures/seplos_v2/ttySC0-interpack-20261026.capture (mbg-bench, listen-only), cross-checked with the CAN 0x355/0x356/0x370 frames of the same bank.

Open register map →
Seplos BMS V3 pack (RTU tap, listen-only)seplos_bms_v3_rtu_tap RTU tap FC01+FC04 / big84
Register map & sources

Read the template description and field notes in the upstream catalog.

Open register map →
Tasmota device (relays, energy, Wi-Fi)tasmota_generic MQTT12
Register map & sources

https://tasmota.github.io/docs/MQTT/

Open register map →
Victron GX (Venus OS) over MQTTvictron_gx_mqtt MQTT38
Register map & sources

https://github.com/victronenergy/dbus-flashmq

Open register map →
Zigbee sensor (zigbee2mqtt)zigbee2mqtt_sensor MQTT6
Register map & sources

https://www.zigbee2mqtt.io/guide/usage/exposes.html

Open register map →

FC03 and FC04 identify Modbus read function codes. Byte/word order, scaling and supported commands belong to the individual template. A map may contain values you do not select for polling.

Source snapshot: 7703820 · 3.98.2

Make missing data and control explicit.

A missing value is not zero.

Virtual meters offer fail, sentinel and time-bounded hold policies. An optional in-band quality block exposes status on the same Modbus connection. Select the behavior your consumer understands.

Virtual meter specification →

Commands start locked.

Enable only the commands your template permits. Bounds, read-back checks and equipment protections apply across command paths. Leases and a safe return value are configured per use case; failed returns are retried and logged.

Command and security documentation →

Separate protection from optimisation.

New rules start in shadow without writes. Local schedules and protective logic can stay in the gateway; plant-wide optimisation belongs to the supervisor you choose.

Rule guide and examples →

From a documented map to a working integration.

  1. Match the device

    Check the model, firmware, interface and source notes. A brand match alone is not enough.

  2. Read before saving

    Use Add Device and its read check. Inspect identity, units and plausible values before creating the device.

  3. Choose the outputs

    Enable MQTT, InfluxDB, OPC UA or virtual meters per device. Confirm the consumer sees the expected values and quality.

  4. Enable control deliberately

    Review write bounds and failure behavior. Observe new rules in shadow before arming them on real equipment.

Your device is not listed?

A documented register map or JSON payload can be used to build a template. Tell us the model, connection and data you need to acquire or control.